Wilkins Water Control Products

Double Check Backflow Preventer Troubleshooting

 
Symptom Probable Cause Remedy
Leaking check valve Debris on seat or seal ring Clean seat area
Damaged seat area Replace check assembly
Damaged seat o-ring Replace seat o-ring
Damaged bolt o-ring(s) on check retainer Replace o-ring(s)
Low or no flow Device installed backwards Verify direction of flow arrow
Gate valves not fully open Turn handles counterclockwise.
Low supply pressure Attach pressure gauge to test cock #1 and verify pressure.