Wilkins Water Control Products

Pilot Operated Pressure Reducing Valve Troubleshooting

 
Symptom Probable Cause Remedy
Main valve won't open No pressure at valve inlet Check inlet pressure
Main valve diaphragm assembly inoperative Disassemble, clean and polish stem, replace defective parts.
Pilot valve (BR4) not opening: (1.) No spring compression, or (2.) Damaged spring. (1.) Tighten adjusting screw. (2.) Disassemble and replace spring.
Flow control disc inoperative. Corrosion or excessive scale buildup on stem. Disassemble, clean and polish stem, replace defective parts.
Main valve fails to close Foreign matter between disc and seat or worn disc. Scale on stem or diaphragm ruptured. Flow clean strainer plugged or isolation valves closed. Disassemble main valve, remove matter, clean parts, and replace defective parts. Remove and clean or replace strainer. Open isolation valves.
Pilot valve (BR4) remains open:  
1. Spring compressed solid 1. Back off adjusting screw
2. Mechanical obstruction 2. Disassemble and remove obstruction
3. Worn seal ring 3. Disassemble remove and replace cartridge assembly
Fails to regulate Air in main valve cover and/or tubing Loosen top cover plug and fittings and bleed air.

Click below for installation and maintenance sheets:

ZW109 Installation and Maintenance sheet
ZW109BP Installation and Maintenance sheet